Codesys Runtime System
CVE-2014-0769
CRITICAL
Severity by source
AV:N/AC:M/Au:N/C:C/I:C/A:C
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
Lifecycle Timeline
1DescriptionCVE.org
The Festo CECX-X-C1 Modular Master Controller with CoDeSys and CECX-X-M1 Modular Controller with CoDeSys and SoftMotion do not require authentication for connections to certain TCP ports, which allows remote attackers to (1) modify the configuration via a request to the debug service on port 4000 or (2) delete log entries via a request to the log service on port 4001.
AnalysisAI
The Festo CECX-X-C1 Modular Master Controller with CoDeSys and CECX-X-M1 Modular Controller with CoDeSys and SoftMotion do not require authentication for connections to certain TCP ports, which. Rated critical severity (CVSS 9.3), this vulnerability is remotely exploitable. No vendor patch available.
Technical ContextAI
This vulnerability is classified as Improper Authentication (CWE-287), which allows attackers to bypass authentication mechanisms to gain unauthorized access. The Festo CECX-X-C1 Modular Master Controller with CoDeSys and CECX-X-M1 Modular Controller with CoDeSys and SoftMotion do not require authentication for connections to certain TCP ports, which allows remote attackers to (1) modify the configuration via a request to the debug service on port 4000 or (2) delete log entries via a request to the log service on port 4001. Affected products include: Softmotion3D Softmotion, Festo Cecx-X-M1 Modular Controller, 3S-Software Codesys Runtime System, Festo Cecx-X-C1 Modular Master Controller.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Implement multi-factor authentication, enforce strong password policies, use proven authentication frameworks.
More in Codesys Runtime System
View allThe Runtime Toolkit in CODESYS Runtime System 2.3.x and 2.4.x does not require authentication, which allows remote attac
The CoDeSys Runtime Toolkit’s file transfer functionality does not perform input validation, which allows an attacker to
The Festo CECX-X-C1 Modular Master Controller with CoDeSys and CECX-X-M1 Modular Controller with CoDeSys and SoftMotion
A Stack-based Buffer Overflow issue was discovered in 3S-Smart CODESYS Web Server. Rated critical severity (CVSS 9.8), t
Runtime Toolkit before 2.4.7.48 in 3S-Smart CODESYS before 2.3.9.48 allows remote attackers to cause a denial of service
Same weakness CWE-287 – Improper Authentication
View allSame technique Authentication Bypass
View allShare
External POC / Exploit Code
Leaving vuln.today