Skip to main content

Phoenix Contact PLCnext EUVDEUVD-2025-209951

| CVE-2025-41670 HIGH
Uncontrolled Search Path Element (CWE-427)
2026-05-27 info@cert.vde.com GHSA-7grg-5m65-97hj
8.7
CVSS 4.0 · Vendor: cert
View

Attack ChainAIDerived

Hypothetical attack flow derived from CVE metadata – not a confirmed exploit chain

  1. Access
    Authenticate as low-privileged local user
  2. Delivery
    Write malicious config/app file to user-writable path
  3. Exploit
    Privileged service loads attacker-controlled file
  4. Execution
    Service acts on it with elevated privileges
  5. Impact
    Full local privilege escalation on controller

Vulnerability Assessment

Weakness
CWE
OWASP Top 10:2025
A08:2025 - Software or Data Integrity Failures
ASVS 5.0
V13 - Configuration Search path element control
Exploitation Conditions

Exploitation requires an authenticated low-privileged local user (CVSS PR:L) who can write to the specific user-writable filesystem locations from which the privileged PLCnext system service loads configuration and application-related files; the attacker must be able to create or modify those files and then have (or wait for) the privileged service process them. Limiting factors: an existing low-privileged foothold/account on the controller is mandatory, no user interaction from a victim is needed (UI:N), and the affected firmware must be earlier than 2026.0.3. Note the data conflict - the CVSS vector lists AV:N (network) but the description describes purely local filesystem manipulation, so a remote unauthenticated path is not supported by the description and the network classification should be confirmed with the vendor.

Impact

Signals here are mixed and should be weighed carefully. CVSS 4.0 rates this 8.7 (High) with full High impact to confidentiality, integrity and availability of the vulnerable component (VC:H/VI:H/VA:H) and PR:L (a valid low-privileged account is required, UI:N). However, the published CVSS vector lists AV:N (network) while the description explicitly states a LOCAL user manipulating local filesystem files - this is a material conflict; the described mechanic is local privilege escalation, so the AV:N classification should be verified against the vendor advisory (VDE-2026-050). EPSS is only 0.03% (9th percentile), there is no KEV listing and no public exploit identified at time of analysis, which argues against imminent mass exploitation. Net: this is a meaningful hardening priority for OT/ICS operators because the affected assets are PLCs and the impact is full compromise of a privileged service, but it is not a drop-everything internet-facing emergency - it requires an existing local foothold, so realistic risk is gated by who already has low-privileged access to these controllers.

Exploit ScenarioDerived

An attacker who already holds a low-privileged account on a PLCnext controller writes a malicious configuration or application file into a user-writable directory that the elevated system service trusts. When that privileged service next reads and processes the planted file, it acts on attacker-controlled content and the attacker gains the service's elevated privileges on the device. No public exploit code is available at time of analysis, and exploitation requires existing local access rather than remote unauthenticated reach.

This Week Schedule remediation this week. Why: HIGH severity (CVSS 7.0-8.9).
Patch available 0.0% exploitation probability (EPSS)

Get an e-mail when this CVE is exploited, patched or re-scored. Free account.

Alert me

AnalysisAIv1 – May 27, 2026

Local privilege escalation in Phoenix Contact PLCnext controllers (AXC F 1152/1252/2152/3152, AXC F 2000 EA, RFC 4072R/4072S, EPC 1522, BPC 9102S, VL3 UPC 2440 EDGE) and the virtual PLCnext Control 500/1000/2000/3000 product lines before firmware 2026.0.3 allows a low-privileged local user to plant or modify configuration and application files in user-writable filesystem locations that a privileged service later consumes, gaining elevated privileges. The flaw (CWE-427) is rated CVSS 4.0 8.7 (High) but carries a very low EPSS of 0.03% (9th percentile). There is no public exploit identified at time of analysis and it is not listed in CISA KEV.

RemediationAI

Vendor-released patch: 2026.0.3 - upgrade all affected PLCnext controllers and Virtual PLCnext Control instances to firmware/version 2026.0.3 or later, as indicated by the EUVD fixed-version boundary and the CERT@VDE advisory VDE-2026-050 (https://www.certvde.com/en/advisories/VDE-2026-050/); confirm the exact patched build against that advisory before deploying to production OT systems. Until patching is feasible, reduce who can reach the local attack surface: restrict and audit low-privileged local accounts on the controllers, since exploitation requires an authenticated low-privileged user, and tighten filesystem permissions on the user-writable directories that the privileged service reads from so they cannot be modified by non-administrative users (trade-off: overly aggressive permission changes can break legitimate application/config workflows and should be validated in a test cell first). Place these controllers on isolated/segmented OT networks with strict access control to limit who can obtain interactive local access in the first place. Treat these as compensating controls only - the firmware update is the actual fix.

Affected VersionsENISA

AXC F 2152 0.0.0 <2026.0.3
VPLCNEXT CONTROL 1000 0.0.0 <2026.0.3
AXC F 1152 0.0.0 <2026.0.3
VPLCNEXT CONTROL 3000 0.0.0 <2026.0.3
VPLCNEXT CONTROL 500 0.0.0 <2026.0.3
VPLCNEXT CONTROL 2000 0.0.0 <2026.0.3
RFC 4072R 0.0.0 <2026.0.3
AXC F 1252 0.0.0 <2026.0.3
RFC 4072S 0.0.0 <2026.0.3
EPC 1522 0.0.0 <2026.0.3
BPC 9102S 0.0.0 <2026.0.3
VL3 UPC 2440 EDGE 0.0.0 <2026.0.3
AXC F 3152 0.0.0 <2026.0.3
AXC F 2000 EA 0.0.0 <2026.0.3

Affected Packages

euvd axc_f_1152 fix: 2026.0.3
euvd axc_f_1252 fix: 2026.0.3
euvd axc_f_2000_ea fix: 2026.0.3
euvd axc_f_2152 fix: 2026.0.3
euvd axc_f_3152 fix: 2026.0.3
euvd bpc_9102s fix: 2026.0.3
euvd epc_1522 fix: 2026.0.3
euvd rfc_4072r fix: 2026.0.3
euvd rfc_4072s fix: 2026.0.3
euvd vl3_upc_2440_edge fix: 2026.0.3
euvd vplcnext_control_1000 fix: 2026.0.3
euvd vplcnext_control_2000 fix: 2026.0.3
euvd vplcnext_control_3000 fix: 2026.0.3
euvd vplcnext_control_500 fix: 2026.0.3

Source: OSV (Open Source Vulnerabilities)

Affects your stack

Affects 14 packages in euvd

Checking this CVE against your own stacks and servers is part of the Basic plan and up.

Technical ContextAI · show details

PLCnext is Phoenix Contact's Linux-based industrial controller runtime used across its AXC F PLC family, RFC/EPC/BPC controllers, edge devices, and the software-only Virtual PLCnext Control variants. The root cause is classified as CWE-427 (Uncontrolled Search Path Element): a system service that runs with elevated privileges loads or processes configuration and application-related files from filesystem paths that are also writable by low-privileged users. Because the service does not adequately restrict or validate the provenance of those files, an attacker-controlled file in a shared/user-writable directory is trusted and acted upon by the privileged process, turning file write access into code/behavior execution at the service's privilege level.

Know when the next one hits your stack

  • Watch products and get an email when something new is published
  • Check this CVE against your own stack and servers
  • Exploit and PoC references, threat intelligence from 22 sources

No credit card · 7-day full trial

Severity by source

Vendor (cert) PRIMARY 8.7 HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

Primary rating from Vendor (cert) · only source for this CVE.

CVSS VectorVendor: cert

Attack Vector
Network
Attack Complexity
Low
Attack Requirements
None
Privileges Required
Low
User Interaction
None
Vulnerable system: Confidentiality
High
Vulnerable system: Integrity
High
Vulnerable system: Availability
High
Subsequent system: Confidentiality
None
Subsequent system: Integrity
None
Subsequent system: Availability
None

Lifecycle Timeline

1
Patch available
May 27, 2026 - 19:46 EUVD

DescriptionCVE.org

A local user with low privileges may be able to influence the behavior of a privileged system service by manipulating configuration or application-related files located in user-writable areas of the filesystem. The affected service processes data from locations that are not sufficiently protected against modification by low-privileged users. As the service runs with elevated privileges, successful exploitation may result in a local privilege escalation.

Executive ViewAI

Why It Matters

Phoenix Contact PLCnext industrial control systems (firmware before version 2026.0.3) contain a local privilege escalation vulnerability enabling low-privileged users to gain elevated system access. This poses operational risk to organizations deploying these controllers, particularly from insider threats or compromised local user accounts.

Business Impact: High
Compensating Controls

Apply vendor patch: Firmware version 2026.0.3 or later. Until patch deployment is complete, restrict local access to affected controllers and implement least-privilege user access controls to minimize privilege escalation risk.

Threat Intelligence Overview

EPSS Score
0.0%
Top 91% exploitable
Data Quality
5 sources
Confidence: Medium

How this decision was reached

The engine reads each signal below and applies a fixed list of rules from top to bottom. The first rule that matches sets the recommended action – like a statement, every line is shown.

SignalValue
Severity HIGH
CISA KEV No
Public POC No
EPSS 0.0%
Patch available Yes
Active threat No
Deciding rule
HIGH severity (CVSS 7.0-8.9)
What every action level means
Emergency Immediate action required. Criteria: CRITICAL + in CISA KEV (actively exploited) without patch, OR CRITICAL + EPSS > 30% without patch, OR CRITICAL + active threat signals without patch.
Act Now Prioritize within 24-48h. Criteria: in KEV with patch available, OR CRITICAL + public POC, OR HIGH + EPSS > 10%, OR CRITICAL + active threat, OR any CRITICAL severity.
This Week Schedule remediation this week. Criteria: HIGH severity (CVSS 7.0-8.9). Patch within normal change window.
This Month Plan within 30 days. Criteria: MEDIUM severity (CVSS 4.0-6.9), lower exploitation probability. Include in regular patch cycle.
Monitor Track and reassess. Criteria: LOW severity (CVSS 0.1-3.9), minimal exploitation risk. No immediate action needed.

SSVC AssessmentENISA

SSVC Decision
Scheduled
Exploitation
None
System Exposure· derived
Open
Automatable
No
Human Impact
High
Technical Impact
Total

Priority Score

44
Low Medium High Critical
KEV: 0
EPSS: 0
CVSS: +44
PoC: 0
Weaponized: 0
Threat intel: 0
Gov advisory: 0

Attack Technique

Privilege escalation occurs when an attacker leverages flaws in access control mechanisms to gain permissions beyond what they were originally granted.

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy