Severity by source
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Lifecycle Timeline
3DescriptionCVE.org
A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V26.10), RTUM85 RTU Base (All versions < V26.10). The affected application contains denial-of-service (DoS) vulnerability. The remote operation mode is susceptible to a resource exhaustion condition when subjected to a high volume of requests. Sending multiple requests can exhaust resources, preventing parameterization and requiring a reset or reboot to restore functionality.
AnalysisAI
Remote denial-of-service in Siemens CPCI85 Central Processing/Communication and RTUM85 RTU Base (versions below V26.10) allows adjacent network attackers to exhaust system resources via high-volume requests, forcing device reset or reboot to restore parameterization functionality. No public exploit identified at time of analysis. CVSS 7.1 (High) with adjacent network access vector and no privileges required indicates moderate real-world risk for industrial environments where these RTU and control processing devices operate.
Technical ContextAI
This vulnerability affects Siemens industrial control system components used in SCADA and RTU deployments: CPCI85 Central Processing/Communication modules (cpe:2.3:a:siemens:cpci85_central_processing/communication) and RTUM85 RTU Base units (cpe:2.3:a:siemens:rtum85_rtu_base). The root cause is CWE-770 (Allocation of Resources Without Limits or Throttling), where the remote operation mode fails to implement rate limiting or request throttling mechanisms. When subjected to a flood of requests from adjacent network positions, the devices experience resource exhaustion that blocks legitimate parameterization operations. The vulnerability requires physical or logical adjacency (CVSS AV:A), suggesting the attack surface is limited to local industrial networks rather than internet-facing exposure.
RemediationAI
Upgrade CPCI85 Central Processing/Communication modules and RTUM85 RTU Base units to version V26.10 or later as specified in Siemens ProductCERT advisory SSA-246443 available at https://cert-portal.siemens.com/productcert/html/ssa-246443.html. Until patching is completed, implement network segmentation to restrict access to these devices from adjacent network segments, deploy intrusion detection systems to monitor for abnormal request volumes targeting the remote operation mode, and apply rate limiting at network perimeter devices where feasible. Consider disabling remote operation mode if not operationally required and enforce strict access controls limiting connections to authorized maintenance systems only.
Out-of-bounds write vulnerabilities in Siemens CPCI85 Central Processing/Communication and SICORE Base system (versions
Privilege escalation in Siemens CPCI85 Central Processing/Communication and SICORE Base System (all versions before V26.
Malicious firmware installation is possible on Siemens CPCI85 Central Processing/Communication firmware (versions before
Denial of service in Siemens CPCI85 Central Processing/Communication firmware and SICORE Base System (all versions befor
Insecure default OPC UA configuration in Siemens CPCI85 Central Processing/Communication and SICORE Base System exposes
Same technique Denial Of Service
View allShare
External POC / Exploit Code
Leaving vuln.today
EUVD-2026-16179