CVE-2025-26389
CRITICALCVSS Vector
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Lifecycle Timeline
2Description
A vulnerability has been identified in OZW672 (All versions < V8.0), OZW772 (All versions < V8.0). The web service in affected devices does not sanitize the input parameters required for the `exportDiagramPage` endpoint. This could allow an unauthenticated remote attacker to execute arbitrary code with root privileges.
Analysis
A vulnerability has been identified in OZW672 (All versions < V8.0), OZW772 (All versions < V8.0). Rated critical severity (CVSS 10.0), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.
Technical Context
This vulnerability is classified as OS Command Injection (CWE-78), which allows attackers to execute arbitrary operating system commands on the host. A vulnerability has been identified in OZW672 (All versions < V8.0), OZW772 (All versions < V8.0). The web service in affected devices does not sanitize the input parameters required for the `exportDiagramPage` endpoint. This could allow an unauthenticated remote attacker to execute arbitrary code with root privileges. Affected products include: Siemens Ozw672 Firmware, Siemens Ozw772 Firmware.
Affected Products
Siemens Ozw672 Firmware, Siemens Ozw772 Firmware.
Remediation
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Avoid passing user input to shell commands. Use language-specific APIs instead of shell execution. Apply strict input validation with allowlists.