Opc Server
CVE-2020-8472
HIGH
Severity by source
AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
Lifecycle Timeline
1DescriptionNVD
Insufficient folder permissions used by system functions in ABB System 800xA products OPCServer for AC800M (versions 6.0 and earlier) and Control Builder M Professional, MMSServer for AC800M, Base Software for SoftControl (version 6.1 and earlier) allow low privileged users to read, modify, add and delete system and application files. An authenticated attacker who successfully exploited the vulnerabilities could escalate his/her privileges, cause system functions to stop and to corrupt user applications.
AnalysisAI
Insufficient folder permissions used by system functions in ABB System 800xA products OPCServer for AC800M (versions 6.0 and earlier) and Control Builder M Professional, MMSServer for AC800M, Base. Rated high severity (CVSS 7.8), this vulnerability is low attack complexity. No vendor patch available.
Technical ContextAI
This vulnerability is classified as Incorrect Permission Assignment (CWE-732), which allows attackers to access resources due to misconfigured permissions. Insufficient folder permissions used by system functions in ABB System 800xA products OPCServer for AC800M (versions 6.0 and earlier) and Control Builder M Professional, MMSServer for AC800M, Base Software for SoftControl (version 6.1 and earlier) allow low privileged users to read, modify, add and delete system and application files. An authenticated attacker who successfully exploited the vulnerabilities could escalate his/her privileges, cause system functions to stop and to corrupt user applications. Affected products include: Abb Control Builder M, Abb Mms Server, Abb Opc Server, Abb Base Software. Version information: version 6.1.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Review and restrict file/resource permissions, apply principle of least privilege.
More in Opc Server
View allA local attacker can gain administrative privileges by inserting an executable file in the path of the affected product.
In the CODESYS Development System multiple components in multiple versions transmit the passwords for the communication
CODESYS Control Runtime system before 3.5.17.0 has improper input validation. Rated high severity (CVSS 7.3), this vulne
Insufficient protection of the inter-process communication functions in ABB System 800xA products OPC Server for AC 800M
Same technique Privilege Escalation