1DescriptionNVD
The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are the idal123 password for the IdalMaster account, and the exor password for the exor account. These credentials are used over both HTTP(S) and FTP. There is no option to disable or change these undocumented credentials. An attacker can use these credentials to login to ABB HMI to read/write HMI configuration files and also to reset the device. This affects ABB CP635 HMI, CP600 HMIClient, Panel Builder 600, IDAL FTP server, IDAL HTTP server, and multiple other HMI components.
AnalysisAI
The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. Rated high severity (CVSS 8.8), this vulnerability is no authentication required, low attack complexity. Public exploit code available and no vendor patch available.
Technical ContextAI
This vulnerability is classified as Use of Hard-coded Credentials (CWE-798), which allows attackers to gain access using credentials embedded in source code. The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are the idal123 password for the IdalMaster account, and the exor password for the exor account. These credentials are used over both HTTP(S) and FTP. There is no option to disable or change these undocumented credentials. An attacker can use these credentials to login to ABB HMI to read/write HMI configuration files and also to reset the device. This affects ABB CP635 HMI, CP600 HMIClient, Panel Builder 600, IDAL FTP server, IDAL HTTP server, and multiple other HMI components. Affected products include: Abb Cp620 Firmware, Abb Cp620-Web Firmware, Abb Cp630 Firmware, Abb Cp630-Web Firmware, Abb Cp635 Firmware.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Remove hard-coded credentials, use environment variables or secrets management, rotate exposed credentials immediately.