1DescriptionNVD
An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Hard-coded SSH keys allow an attacker to gain unauthorised access or disclose encrypted data on the RTU due to the keys not being regenerated on initial installation or with firmware updates. In other words, these devices use private-key values in /etc/ssh/ssh_host_rsa_key, /etc/ssh/ssh_host_ecdsa_key, and /etc/ssh/ssh_host_dsa_key files that are publicly available from the vendor web sites.
AnalysisAI
An issue was discovered on Mitsubishi Electric Europe B.V. Rated critical severity (CVSS 9.8), this vulnerability is remotely exploitable, no authentication required, low attack complexity. Public exploit code available and no vendor patch available.
Technical ContextAI
This vulnerability is classified as Use of Hard-coded Credentials (CWE-798), which allows attackers to gain access using credentials embedded in source code. An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Hard-coded SSH keys allow an attacker to gain unauthorised access or disclose encrypted data on the RTU due to the keys not being regenerated on initial installation or with firmware updates. In other words, these devices use private-key values in /etc/ssh/ssh_host_rsa_key, /etc/ssh/ssh_host_ecdsa_key, and /etc/ssh/ssh_host_dsa_key files that are publicly available from the vendor web sites. Affected products include: Mitsubishielectric Smartrtu Firmware, Inea Me-Rtu Firmware. Version information: through 2.02.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Remove hard-coded credentials, use environment variables or secrets management, rotate exposed credentials immediately.
More in Smartrtu Firmware
View allAn issue was discovered on Mitsubishi Electric Europe B.V. Rated critical severity (CVSS 9.8), this vulnerability is rem
An issue was discovered on Mitsubishi Electric Europe B.V. Rated critical severity (CVSS 9.8), this vulnerability is rem
An issue was discovered on Mitsubishi Electric Europe B.V. Rated critical severity (CVSS 9.8), this vulnerability is rem
An issue was discovered on Mitsubishi Electric Europe B.V. Rated high severity (CVSS 7.5), this vulnerability is remotel
An issue was discovered on Mitsubishi Electric Europe B.V. Rated medium severity (CVSS 6.5), this vulnerability is remot
An issue was discovered on Mitsubishi Electric Europe B.V. Rated medium severity (CVSS 5.4), this vulnerability is remot
Same weakness CWE-798 – Use of Hard-coded Credentials
View allSame technique Authentication Bypass
View allShare
External POC / Exploit Code
Leaving vuln.today