Skip to main content

Ec 61850 System Configurator Firmware CVE-2018-4858

HIGH
Improper Access Control (CWE-284)
2018-07-09 productcert@siemens.com
7.8
CVSS 3.1 · NVD
Share

Severity by source

NVD PRIMARY
7.8 HIGH
AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
Attack Vector
Local
Attack Complexity
Low
Privileges Required
None
User Interaction
Required
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

Lifecycle Timeline

1
CVE Published
Jul 09, 2018 - 19:29 nvd
HIGH 7.8

DescriptionNVD

A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.

AnalysisAI

A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All. Rated high severity (CVSS 7.8), this vulnerability is no authentication required, low attack complexity. No vendor patch available.

Technical ContextAI

This vulnerability is classified under CWE-284. A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue. Affected products include: Siemens Ec 61850 System Configurator Firmware, Siemens Sicam Pq Analyzer Firmware, Siemens Sicam Scc Firmware, Siemens Digsi 4 Firmware, Siemens Digsi 5 Firmware.

RemediationAI

No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.

Share

CVE-2018-4858 vulnerability details – vuln.today

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy