Skip to main content

Simatic Wincc Open Architecture CVE-2018-13799

CRITICAL
Improper Privilege Management (CWE-269)
2018-09-12 productcert@siemens.com
9.1
CVSS 3.0 · NVD
Share

Severity by source

NVD PRIMARY
9.1 CRITICAL
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H

Primary rating from NVD · only source for this CVE.

CVSS VectorNVD

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H
Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
High
Availability
High

Lifecycle Timeline

1
CVE Published
Sep 12, 2018 - 13:29 nvd
CRITICAL 9.1

DescriptionNVD

A vulnerability has been identified in SIMATIC WinCC OA V3.14 and prior (All versions < V3.14-P021). Improper access control to a data point of the affected product could allow an unauthenticated remote user to escalate its privileges in the context of SIMATIC WinCC OA V3.14. This vulnerability could be exploited by an attacker with network access to port 5678/TCP of the SIMATIC WinCC OA V3.14 server. Successful exploitation requires no user privileges and no user interaction. This vulnerability could allow an attacker to compromise integrity and availability of the SIMATIC WinCC OA system. At the time of advisory publication no public exploitation of this vulnerability was known.

AnalysisAI

A vulnerability has been identified in SIMATIC WinCC OA V3.14 and prior (All versions < V3.14-P021). Rated critical severity (CVSS 9.1), this vulnerability is remotely exploitable, no authentication required, low attack complexity. No vendor patch available.

Technical ContextAI

This vulnerability is classified as Improper Privilege Management (CWE-269), which allows attackers to escalate privileges to gain unauthorized elevated access. A vulnerability has been identified in SIMATIC WinCC OA V3.14 and prior (All versions < V3.14-P021). Improper access control to a data point of the affected product could allow an unauthenticated remote user to escalate its privileges in the context of SIMATIC WinCC OA V3.14. This vulnerability could be exploited by an attacker with network access to port 5678/TCP of the SIMATIC WinCC OA V3.14 server. Successful exploitation requires no user privileges and no user interaction. This vulnerability could allow an attacker to compromise integrity and availability of the SIMATIC WinCC OA system. At the time of advisory publication no public exploitation of this vulnerability was known. Affected products include: Siemens Simatic Wincc Open Architecture.

RemediationAI

No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply principle of least privilege, validate privilege transitions, implement proper role separation.

Share

CVE-2018-13799 vulnerability details – vuln.today

This site uses cookies essential for authentication and security. No tracking or analytics cookies are used. Privacy Policy