Ipc Diagnostics
CVE-2015-4051
CRITICAL
Severity by source
AV:N/AC:L/Au:N/C:P/I:P/A:C
Primary rating from NVD · only source for this CVE.
CVSS VectorNVD
AV:N/AC:L/Au:N/C:P/I:P/A:C
Lifecycle Timeline
1DescriptionCVE.org
Beckhoff IPC Diagnostics before 1.8 does not properly restrict access to functions in /config, which allows remote attackers to cause a denial of service (reboot or shutdown), create arbitrary users, or possibly have unspecified other impact via a crafted request, as demonstrated by a beckhoff.com:service:cxconfig:1#Write SOAP action to /upnpisapi.
AnalysisAI
Beckhoff IPC Diagnostics before 1.8 does not properly restrict access to functions in /config, which allows remote attackers to cause a denial of service (reboot or shutdown), create arbitrary users,. Rated critical severity (CVSS 9.0), this vulnerability is remotely exploitable, low attack complexity. Public exploit code available and no vendor patch available.
Technical ContextAI
This vulnerability is classified under CWE-284. Beckhoff IPC Diagnostics before 1.8 does not properly restrict access to functions in /config, which allows remote attackers to cause a denial of service (reboot or shutdown), create arbitrary users, or possibly have unspecified other impact via a crafted request, as demonstrated by a beckhoff.com:service:cxconfig:1#Write SOAP action to /upnpisapi. Affected products include: Beckhoff Ipc Diagnostics. Version information: before 1.8.
RemediationAI
No vendor patch is available at time of analysis. Monitor vendor advisories for updates. Apply vendor patches when available. Implement network segmentation and monitoring as interim mitigations.
Same weakness CWE-284 – Improper Access Control
View allSame technique Denial Of Service
View allShare